Model 267/267MR
Applications
- Heating, Ventilating and
Air-Conditioning (HVAC)
- Energy Management
Systems
- Static Duct Pressure
- Clean Room Pressure
- Oven Pressurization and
Furnace Draft Controls
Features
- Model 267MR Offers
Multi-Range Capability,
6 Field Selectable
Ranges via Dip Switches,
and Field Selectable 0-5
or 0-10 VDC Output
- Model 267 Offers an
Optional 3 1/2 Digit
LCD Display with a
0.5% FS Standard
Accuracy
- NEMA 4/IP65 Rated
Housing
- Optional Accuracies as
High as 0.25% FS
- 24 VAC or 24 VDC
Excitation
- PG-9, PG13.5 or Conduit
Electrical Termination
- Integral Static
Pressure Probe
- Ranges as low as 0.1 in.
W.C. (25 Pa)
- Meets CE Conformance
Standards
|
|
Setra Systems Model 267 and 267MR
pressure transducers sense gauge
(static) or differential pressure and
convert this pressure difference to a
proportional electrical output. The 267
series is offered with a high level voltage
output or 4-20 mA current output. The
267MR offers multi-range capability and
field configurable 0-5 VDC or 0-10 VDC
output, as well as a 4-20 mA output. The
267 is a single range unit and offers an
optional LCD display. The 267 series has an
IP65/NEMA 4 rated package to withstand
environmental effects.
The 267 Series is available with an optional
integral static pressure probe. Installation
is quick and easy by mounting this version
directly onto the duct. The 0.25" diameter
pressure probe is made of sturdy extruded
aluminum and is designed with baffles to
prevent any velocity pressure errors.
Used in Building Energy Management
Systems, the 267 and 267MR pressure
transducers are available for air pressure
ranges as low as 0.1 in W.C. (25 Pa) full scale
to 100 in. W.C. (25 kPa) full scale. Static
accuracy is ±1% full scale in normal
ambient temperature environments.
The 267 series utilizes an improved all
stainless steel micro-tig welded sensor,
which is enclosed in a welded stainless steel
body. The tensioned stainless steel diaphragm
and insulated stainless steel
electrode, positioned close to the diaphragm,
form a variable capacitor. As the
pressure increases or decreases, the capacitance
changes. The change in capacitance is
detected and converted to a linear DC
electrical signal by Setra's unique electronic
circuit.
The micro-tig welded tension sensor
allows up to 10 psi overpressure (in either
direction), with no damage to the unit. The
improved sensor design also allows the
Model 267MR version to have 6 field
selectable pressure ranges (bi-directional
and unidirectional) in one unit. With
minimal effort, the user can field calibrate
the unit with a fiip of a switch and be
assured of optimum performance.
|